CVE-2021-22659
—CVSS 3.1
8.6 high
EPSS
2%p76
Published
()
Modified
Description
Rockwell Automation MicroLogix 1400 Version 21.6 and below may allow a remote unauthenticated attacker to send a specially crafted Modbus packet allowing the attacker to retrieve or modify random values in the register. If successfully exploited, this may lead to a buffer overflow resulting in a denial-of-service condition. The FAULT LED will flash RED and communications may be lost. Recovery from denial-of-service condition requires the fault to be cleared by the user.
- Vendors
- rockwellautomation
- Products
- micrologix 1400 firmware
- Weakness
- CWE-120
- Vector
- CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H
In the news0 stories
No ingested article mentions this CVE yet.