Description

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 = V2.3 < V6.30.37), Nucleus NET for Nucleus PLUS V1 (All versions < V5.2a), Nucleus NET for Nucleus PLUS V2 (All versions < V5.4), Nucleus ReadyStart V3 V2012 (All versions < V2012.08.1), Nucleus ReadyStart V3 V2017 (All versions < V2017.02.4), Nucleus Source Code (All versions including affected FTP server), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The FTP server does not properly release memory resources that were reserved for incomplete connection attempts by FTP clients. This could allow a remote attacker to generate a denial of service condition on devices that incorporate a vulnerable version of the FTP server.

Vendors
siemens
Products
nucleus net, nucleus readystart v3, nucleus source code, apogee modular building controller firmware, apogee modular equiment controller firmware, apogee pxc compact firmware, apogee pxc modular firmware, desigo pxc00-e.d firmware, desigo pxc00-u firmware, desigo pxc001-e.d firmware, desigo pxc12-e.d firmware, desigo pxc22-e.d firmware
Weakness
CWE-400, CWE-401
Vector
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

In the news

No ingested article mentions this CVE yet.