ZeroHour

CVE-2025-13824

CVSS 4.0
8.7 high
EPSS
<1%p27
Published
()
Modified
Description

A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.

Weakness
CWE-763
Vector
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

In the news

No ingested article mentions this CVE yet.