ZeroHour
The Hacker Newspublished ()ingested @TheHackersNews

CISA Warns of Multiple Critical Vulnerabilities Affecting Mitsubishi Electric PLCs

Vulnerabilities mentionedAll →

CVEVulnerabilityCVSSEPSSFlagsAffectedExposurePublished
CVE-2022-29830
+2 in the same advisory: …29831 …25164
Use of Hard-coded Cryptographic Key vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.095Z, and Motion Control Setting(GX Works3 related

Use of Hard-coded Cryptographic Key vulnerability in Mitsubishi Electric GX Works3 versions from 1.000A to 1.095Z, and Motion Control Setting(GX Works3 related software) versions from 1.000A to 1.065T allows a remote unauthenticated attacker to disclose or tamper with sensitive information. As a result, unauthenticated attackers may obtain information about project files illegally.

NVD description · AI analysis pending
9.1
group max
1%
  • mitsubishielectric gx works3
CVE-2022-2641
Horner Automation’s RCC 972 with firmware version 15.40 has a static encryption key on the device.

Horner Automation’s RCC 972 with firmware version 15.40 has a static encryption key on the device. This could allow an attacker to perform unauthorized changes to the device, remotely execute arbitrary code, or cause a denial-of-service condition.

NVD description · AI analysis pending
9.8<1%
  • hornerautomation rcc972 firmware
CVE-2022-40265
Improper Input Validation vulnerability in Mitsubishi Electric Corporation MELSEC iQ-R Series RJ71EN71 Firmware version "65" and prior and Mitsubishi Electric C

Improper Input Validation vulnerability in Mitsubishi Electric Corporation MELSEC iQ-R Series RJ71EN71 Firmware version "65" and prior and Mitsubishi Electric Corporation MELSEC iQ-R Series R04/08/16/32/120ENCPU Network Part Firmware version "65" and prior allows a remote unauthenticated attacker to cause a Denial of Service condition by sending specially crafted packets. A system reset is required for recovery.

NVD description · AI analysis pending
7.5<1%
  • mitsubishielectric rj71en71 firmware
  • mitsubishielectric r04encpu firmware
  • mitsubishielectric r08encpu firmware
  • +1 more
Full article410 words · extracted from thehackernews.com · click to collapse

Ravie LakshmananDec 02, 2022ICS Security / Encryption

The U.S. Cybersecurity and Infrastructure Security Agency (CISA) this week released an Industrial Control Systems (ICS) advisory warning of multiple vulnerabilities in Mitsubishi Electric GX Works3 engineering software.

"Successful exploitation of these vulnerabilities could allow unauthorized users to gain access to the MELSEC iQ-R/F/L series CPU modules and the MELSEC iQ-R series OPC UA server module or to view and execute programs," the agency said.

GX Works3 is an engineering workstation software used in ICS environments, acting as a mechanism for uploading and downloading programs from/to the controller, troubleshooting software and hardware issues, and performing maintenance operations.

The wide range of functions also makes the platform an attractive target for threat actors looking to compromise such systems to commandeer the managed PLCs.

Three of the 10 shortcomings relate to cleartext storage of sensitive data, four relate to the use of a hard-coded cryptographic key, two relate to the use of a hard-coded password, and one concerns a case of insufficiently protected credentials.

The most critical of the bugs, CVE-2022-25164, and CVE-2022-29830, carry a CVSS score of 9.1 and could be abused to gain access to the CPU module and obtain information about project files without requiring any permissions.

Nozomi Networks, which discovered CVE-2022-29831 (CVSS score: 7.5), said an attacker with access to a safety PLC project file could exploit the hard-coded password to directly access the safety CPU module and potentially disrupt industrial processes.

"Engineering software represents a critical component in the security chain of industrial controllers," the company said. "Should any vulnerabilities arise in them, adversaries may abuse them to ultimately compromise the managed devices and, consequently, the supervised industrial process."

The disclosure comes as CISA revealed details of a denial-of-service (DoS) vulnerability in Mitsubishi Electric MELSEC iQ-R Series that stems from a lack of proper input validation (CVE-2022-40265, CVSS score: 8.6).

"Successful exploitation of this vulnerability could allow a remote unauthenticated attacker to cause a denial-of-service condition on a target product by sending specially crafted packets," CISA noted.

In a related development, the cybersecurity agency further outlined three issues impacting Remote Compact Controller (RCC) 972 from Horner Automation, the most critical of which (CVE-2022-2641, CVSS score: 9.8) could lead to remote code execution or cause a DoS condition.

Found this article interesting? Follow us on Google News, Twitter and LinkedIn to read more exclusive content we post.