CISA tells operators to harden Siemens S7 PLCs. Here’s how to do it without disrupting production
CISA, NSA, FBI and other agencies warn of active targeting of internet-exposed Siemens S7 PLCs and urge patching, exposure removal and hardening.
Joint advisory AA26-231A from the NSA, CISA, FBI, Department of Energy and EPA warns that actors are actively targeting Siemens S7 PLCs using internet scanning, AI-assisted scripts and libraries such as Snap7 and python-snap7 over S7comm on TCP port 102. The advisory covers S7-200 through S7-1500 series controllers and recommends patching, removing internet exposure, access controls, monitoring and disabling unneeded services. Siemens states no new S7 vulnerabilities are involved, only misconfigurations addressed in existing ProductCERT guidance SSB-104599. The article details how to apply each measure without breaking production dependencies such as remote I/O, HMI links and diagnostics.
Schneider Electric Easergy, EcoStruxture, PowerLogic, and Saitel Products (Update A)
CISA updated ICSA-26-169-07: CVE-2026-4827 (CVSS 8.3) insufficient entropy enables session hijacking across dozens of Schneider Electric grid products; fixes available.
CISA republished advisory ICSA-26-169-07 (Update A) for CVE-2026-4827, CWE-331 insufficient entropy in session management, scored CVSS 8.3. Affected lines include Easergy MiCOM relays and C5, EcoStruxure Power Automation (EPAS-GTW, EPAS-UI, iPMFLS), EcoStruxure Power Operation, PowerLogic P5/P7/T300/T500, and Saitel DP/T150 RTUs, with dozens of fixed versions listed. Successful exploitation could enable session hijacking and unauthorized operations on systems in energy, chemical, critical manufacturing, and water sectors. Fixes are available; no exploitation is reported.