PowerSYSTEM Center flaws allow SQL injection and admin resource access
Original title: Subnet Solutions PowerSYSTEM Center
Both CVEs score 9.0; Subnet tells 2020 users to install Update 30 and later lines to install 2026 Update 1.1.
CISA advisory ICSA-26-307-01 covers two critical flaws in Subnet Solutions PowerSYSTEM Center, deployed in energy and critical manufacturing. CVE-2026-63017 lets a low-privileged authenticated user reach administrator-only resources. CVE-2026-63774 lets an authenticated user run unauthorized SQL from the report designer. Vendor fixes are 2020 Update 30 and 2026 Update 1.1; the advisory does not discuss exploitation.
Unconfirmed: The body also marks 2020 known_affected under CVE-2026-63774, while the summary lists only CVE-2026-63017 for that line; exploitation is not addressed.
- CVE-2026-63017 affects 2020 <=5.29.x, 2024 6.0.x–6.2.x, and 2026 7.0.x–7.1.x.
- The summary lists CVE-2026-63774 for 2024 and 2026 builds only.
- CVSS v3.1 is 9.0 and CVSS v4.0 is 9.4, adjacent network with low privileges.
- Subnet is headquartered in Canada; deployments are described as worldwide.
Impact: Authenticated users run SQL or reach admin-only resources
| Product | Affected | Fixed in |
|---|---|---|
| Subnet Solutions PowerSYSTEM Center 2020 | <=5.29.x | 2020 Update 30 |
| Subnet Solutions PowerSYSTEM Center 2024 | >=6.0.x|<=6.2.x | 2026 Update 1.1 |
| Subnet Solutions PowerSYSTEM Center 2026 | >=7.0.x|<=7.1.x | 2026 Update 1.1 |
- 1.Upgrade PowerSYSTEM Center 2020 to Update 30.
- 2.Upgrade 2024 and 2026 builds to PowerSYSTEM Center 2026 Update 1.1.
- 3.If unable to update, disable report designer and F12 Developer Tools access and monitor user activity.
- Vendors
- Subnet Solutions
- Products
- PowerSYSTEM Center
- Organizations
- CISA
- Countries
- Canada
Vulnerabilities mentioned
All| CVE | Vulnerability | CVSS | EPSS | Signals | Published |
|---|---|---|---|---|---|
CVE-2026-63017+1 related CVE | Incorrect authorization in PowerSYSTEM Center allows low-privileged authenticated access | 9.4 | — |
From the original article
5 min read at cisa.govView CSAF Summary Successful exploitation of these vulnerabilities could allow an attacker to execute unauthorized SQL commands and gain access to unauthorized resources. The following versions of Subnet Solutions PowerSYSTEM Center are affected: PowerSYSTEM Center 2020 =6. 0.
By CISA · cisa.gov
A short excerpt; the article and its images belong to the publisher. Summary, key facts and assessment above are AI-written from the article and can be wrong.