Siemens WTV676 and WTV776
Siemens WTV676 and WTV776 have an unauthenticated remote flaw that can disable web access.
CISA republished Siemens ProductCERT SSA-823812 as ICSA-26-265-08 for Siemens WTV676 and WTV776. CVE-2026-89207 is improper validation of input from backend services in the WTV676-HB6035 web interface before 3.94 and the WTV776-HB6035 web interface before 4.17. An unauthenticated remote attacker can force the device into protection mode and disable Web Access. CVSS v3.1 is 6.5 Medium; Siemens recommends updating, and the advisory does not report known exploitation.
- CVE-2026-89207 affects WTV676 web interface before 3.94 and WTV776 before 4.17.
- Unauthenticated remote input can force protection mode and disable Web Access.
- CVSS v3.1 is 6.5 Medium; devices are used in the energy sector worldwide.
- Siemens released fixes; CISA republished ProductCERT advisory SSA-823812.
Vulnerabilities mentionedAll →
- CVE-2026-892076.9—DoS via Unauthenticated Input Validation Flaw in Siemens WTV Devicespublished · Siemens WTV676-HB6035 Web Interface
| CVE | Vulnerability | CVSS | EPSS | Flags | Affected | Exposure | Published |
|---|---|---|---|---|---|---|---|
| CVE-2026-89207 | DoS via Unauthenticated Input Validation Flaw in Siemens WTV Devices CVE-2026-89207 is a vulnerability in Siemens WTV676 and WTV776 series network devices that allows an unauthenticated remote attacker to force the device into protection mode via malicious input to backend services. This denial-of-service condition disrupts the device's remote web management interface. The flaw affects specific web interface versions of the WTV676-HB6035 and WTV776-HB6035 models. There is currently no known public proof-of-concept or in-the-wild exploitation. Do: Upgrade affected WTV676-HB6035 models to version V3.94 or later and WTV776-HB6035 models to version V4.17 or later as soon as patches are available. If an upgrade is not immediately possible, restrict network access to these devices to trusted internal networks only. Monitor for any unusual loss of remote web access connectivity as a potential indicator of exploitation. |
Full article637 words · extracted from cisa.gov · click to collapse
Summary
The products listed below contain a denial of service vulnerability that could allow an attacker to force the devices into protection mode under certain conditions. This disables remote connectivity functions (Web Access) to the devices. Siemens has released new versions for the affected products and recommends to update to the latest versions.
The following versions of Siemens WTV676 and WTV776 are affected:
- WTV676-HB6035 Web Interface vers:intdot/<3.94 (CVE-2026-89207)
- WTV776-HB6035 Web Interface vers:intdot/<4.17 (CVE-2026-89207)
| CVSS | Vendor | Equipment | Vulnerabilities |
|---|---|---|---|
| v3 6.5 | Siemens | Siemens WTV676 and WTV776 | Improper Validation of Specified Type of Input |
Background
- Critical Infrastructure Sectors: Energy
- Countries/Areas Deployed: Worldwide
- Company Headquarters Location: Germany
Vulnerabilities
CVE-2026-89207
Affected devices do not properly validate input received from backend services. This could allow an unauthenticated remote attacker to force the device into protection mode, which results in losing remote connectivity functions (Web Access).
Affected Products
Siemens WTV676 and WTV776
Vendor:
Siemens
Product Version:
WTV676-HB6035 Web Interface < V3.94, WTV776-HB6035 Web Interface < V4.17
Product Status:
known_affected
Relevant CWE: CWE-1287 Improper Validation of Specified Type of Input
Metrics
| CVSS Version | Base Score | Base Severity | Vector String |
|---|---|---|---|
| 3.1 | 6.5 | MEDIUM | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L |
Acknowledgments
- Siemens ProductCERT reported this vulnerability to CISA.
General Recommendations
As a general security measure Siemens strongly recommends protecting network access to affected products with appropriate mechanisms. It is advised to follow recommended security practices in order to run the devices in a protected IT environment.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.
- Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.
- Locate control system networks and remote devices behind firewalls and isolate them from business networks.
- When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Siemens ProductCERT SSA-823812 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Siemens ProductCERT directly for any questions regarding this advisory.
Revision History
- Initial Release Date: 2026-09-16
| Date | Revision | Summary |
|---|---|---|
| 2026-09-16 | 1 | Publication Date |
| 2026-09-22 | 2 | Initial CISA Republication of Siemens ProductCERT SSA-823812 advisory |