ZeroHour

Search: “Cyber Security Situation Center”

60 stories

FrostyGoop’s Zoom-In: A Closer Look into the Malware Artifacts, Behaviors and Network Communications

Unit 42 dissects FrostyGoop OT malware, which sent Modbus TCP commands to disrupt heating for 600+ apartment buildings in Ukraine.

Palo Alto Unit 42 analyzed new FrostyGoop/BUSTLEBERM samples, the ninth known ICS-centric malware, first used against a Ukrainian municipal energy company by sending Modbus TCP commands to ENCO control devices. The attack caused a two-day heating outage affecting over 600 apartment buildings during sub-zero temperatures. The Go-compiled malware accepts Modbus register operations and timing parameters via command-line arguments or a JSON configuration file, uses an obscure open-source Modbus library, and checks the Windows BeingDebugged flag to evade debuggers. Unit 42 telemetry recorded over 1 million Modbus TCP devices exposed to the internet between September and October 2024.

Palo Alto Unit 42 · 28d agoMalware in the wild

Schneider Electric SCADAPack x70 Products

CISA advisory: Schneider Electric SCADAPack x70 RTUs contain CVE-2026-81861, an insufficiently protected credentials flaw allowing unauthorized access to RTU configuration.

CISA advisory ICSA-26-258-04 discloses CVE-2026-81861 affecting all versions of Schneider Electric SCADAPack 47x, 47xi, 47xd, 470R, 57x, 3xx, and 32 remote terminal units. The CWE-522 insufficiently protected credentials vulnerability could expose authentication information and permit unauthorized access to RTU configuration through the Secure Lock functionality. The flaw carries a CVSS v3.1 base score of 6.5 (medium), and the products are deployed worldwide in critical manufacturing and energy sectors. Abhinav Agarwal reported the vulnerability to CISA.

CISA Advisories · 1d agoAdvisoryCVE-2026-81861