Schneider Electric SCADAPack x70 Products
CISA advisory: Schneider Electric SCADAPack x70 RTUs contain CVE-2026-81861, an insufficiently protected credentials flaw allowing unauthorized access to RTU configuration.
CISA advisory ICSA-26-258-04 discloses CVE-2026-81861 affecting all versions of Schneider Electric SCADAPack 47x, 47xi, 47xd, 470R, 57x, 3xx, and 32 remote terminal units. The CWE-522 insufficiently protected credentials vulnerability could expose authentication information and permit unauthorized access to RTU configuration through the Secure Lock functionality. The flaw carries a CVSS v3.1 base score of 6.5 (medium), and the products are deployed worldwide in critical manufacturing and energy sectors. Abhinav Agarwal reported the vulnerability to CISA.
AVEVA Pipeline Integrity Monitor
CISA advisory details four flaws in AVEVA Pipeline Integrity Monitor <=2025_SP1_P1, allowing information disclosure, weak-hash admin elevation, and cross-site scripting.
CISA published ICSA-26-253-01 covering AVEVA Pipeline Integrity Monitor versions <=2025_SP1_P1_build_7.1.9580.8513. CVE-2026-81821 (hard-coded cryptographic key, CWE-321) lets a user with read access decrypt PIMBoards project files, and CVE-2026-81822 (CWE-327) allows brute-forcing weak password hashes to elevate to PIMBoards administrator; both score 8.4 HIGH (CVSS v3.1). CVE-2026-81823 (CWE-862) permits unauthenticated read operations, and CVE-2026-81824 (CWE-79) enables arbitrary JavaScript execution via socially engineered links. CISA reports no known public exploitation and recommends limiting network exposure of control system devices.