Skip to content
NewA calmer, faster ZeroHour

CVE-2026-27873

Hard-coded credentials in Johnson Controls EasyIO FG

CVSS 4.0
5.6 medium
EPSS
—
Published
·
Modified
Analyze CVE-2026-27873 with Vani AIImpact, affected versions, exploitation status, mitigations and detection

Johnson Controls EasyIO FG building-automation controllers before version 2.0b52 contain hard-coded credentials (CWE-798). A local attacker who already has low privileges can use those embedded credentials in a password-spraying attempt; the vendor rates the attack as high complexity and dependent on specific conditions, with no user interaction required. Successful use can cause high integrity and availability impact on the controller and high confidentiality, integrity, and availability impact on subsequent systems, while confidentiality of the vulnerable device itself is rated low. The issue is scored CVSS 4.0 5.6 (medium) largely because the attack is local and constrained. It is not listed in CISA KEV, and no public proof-of-concept is known.

What to do: Upgrade every EasyIO FG controller to version 2.0b52 or later. Until that is done, restrict local access to the devices, replace any built-in or default credentials, and review local login and configuration-change logs for unauthorized use.

ProductAffected
Johnson Controls EasyIO FGbefore 2.0b52
Estimated exposure
No basis for an estimate.

Order-of-magnitude estimate by the model from install counts, market share and public scan data it knows; verify before quoting.

Description · NVD

- Use of Hard-coded Credentials vulnerability in Johnson Controls EasyIO FG allows - Pasword Spraying. This issue affects EasyIO FG: before 2.0b52.

Weakness
CWE-798
Vector
CVSS:4.0/AV:L/AC:H/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:H/SI:H/SA:H/E:P/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

In the news

1 story