Hitachi Energy RTU500
CISA warns end-of-life Hitachi Energy RTU500 firmware has critical unauthenticated flaws, including arbitrary firmware upload.
Authenticated reboot via improper authorization in Hitachi Energy RTU500
CVE-2026-8067 is an improper authorization flaw (CWE-862) in the web application of end-of-life Hitachi Energy RTU500 units. An authenticated, low-privileged user on the network can call the reset endpoint and force the RTU to reboot. Successful use causes temporary device unavailability and can disrupt the RTU’s intended operation; confidentiality and integrity are not affected (CVSS 3.1 base score 6.5, availability high). Only end-of-life RTU500 versions are described as affected; exact version numbers are not stated. It is not listed in CISA KEV, and no public proof-of-concept is known.
What to do: Treat end-of-life RTU500 units as unsupported: plan replacement or migration to a currently supported Hitachi Energy RTU release, and until then limit the web application to trusted management networks and accounts. Review who holds authenticated access, and alert on unexpected reboots or use of the reset function. No fixed version number is given in the advisory data.
| Product | Affected |
|---|---|
| Hitachi Energy RTU500 | — |
Order-of-magnitude estimate by the model from install counts, market share and public scan data it knows; verify before quoting.
An improper authorization vulnerability in the end-of-life versions of RTU500’s web application allows an authenticated user to trigger the RTU500 to reboot through the reset endpoint. Successful exploitation could cause temporary device unavailability and disruption of its intended operation.
CISA warns end-of-life Hitachi Energy RTU500 firmware has critical unauthenticated flaws, including arbitrary firmware upload.
Today 234 readers · 245 views · 31 reads · all time 215K views