Skip to content
NewA calmer, faster ZeroHour
StoryVulnerabilityhigh

Unpatched Danfoss AK-SM800A flaws allow remote takeover without login

5 sources · 5 articlesFirst reported Updated ()1
What's new

First merged summary.

Merged summary · x-ai/grok-4.7 · rewritten as coverage arrivesSummaries by Vani AI

Six unpatched Danfoss AK-SM800A flaws can allow unauthenticated remote takeover; agencies urge operators to remove internet exposure.

Midnight Blue researcher Carlo Meijer reported six pre-authentication flaws in Danfoss AK-SM800A refrigeration controllers that can let a remote attacker take control without logging in. Five sit in web handlers of a root-running program; the sixth is in the gateway that enforces Strict mode, on by default since version 4.0. Researchers say versions through 5.3.2 are affected and that 5.4.0 does not fix them; no CVEs or patches are available. Security Affairs reports the German BSI first called 5.4.0 unaffected, then said it could not rule that out. Belgian, Irish and German agencies urge operators to take management interfaces off the internet; the BSI says it has no information the six flaws are being exploited.

Key facts
  • No CVEs or vendor patches; researchers say firmware 5.4.0 remains vulnerable.
  • Five bugs need no login; the sixth remains with Strict mode enabled.
  • No secure boot, stack canaries or PIE; root code can survive reset and update.
  • Researchers ran code as root on firmware 3.3.0 and found the same bugs in 5.3.2.
  • The BSI says it has no information these six flaws are being exploited.
  • Belgian and Irish agencies advise checking temperatures, defrost schedules, alarms and accounts.
Analyze this story with Vani AIImpact, who is affected and what defenders should do, in a new chat

What each outlet adds

beyond the shared facts
  • The Hacker NewsRoot execution on 3.3.0; gateway flaw crashed 5.3.2 in an emulator.
  • The RegisterDanfoss did not reply; CCB warns of control, persistence or disabling units.
  • Security AffairsBSI reversed its 5.4.0 claim; Censys sees hundreds of Danfoss systems online.

Coverage

oldest first · one row per article · UTC
  1. · 6d ago The Hacker NewsFirst report

    Six unpatched Danfoss AK-SM800A flaws allow login-free takeover

    Belgian, Irish, and German agencies say operators should take management interfaces off the internet now.

  2. · 6d ago SOCRadar

    Unpatched Danfoss AK-SM800A flaws allow takeover

    The supplied page text is site navigation and gives no versions, CVE ids or patch status.

  3. · 5d ago The Register · Security

    Researcher reports six zero-days in Danfoss AK-SM800A 5.3.2

    Belgium's CCB says the flaws could allow unauthenticated control, persistence after a reset, or disabling the controllers.

  4. · 5d ago Security Affairs

    Six unpatched pre-auth RCE flaws found in Danfoss AK-SM800A

    Versions through 5.3.2 are affected; BSI says these six bugs are not known to be exploited.

  5. · 2d ago Hacker News · security

    UK teams take supermarket fridge controllers offline after flaw find

    RDM says no malicious activity was seen and has shipped first patches after a weak-password issue was found.