Skip to content
NewA calmer, faster ZeroHour
StoryVulnerabilityhigh

Six unpatched pre-auth RCEs found in Danfoss AK-SM800A firmware

2 sources · 2 articlesFirst reported Updated ()1
What's new

First merged summary.

Merged summary · x-ai/grok-4.7 · rewritten as coverage arrivesSummaries by Vani AI

Six pre-auth stack overflows affect all Danfoss AK-SM800A firmware through 5.3.2; CVEs are still pending.

Midnight Blue found six pre-authentication remote code execution flaws, all stack-based buffer overflows, in Danfoss AK-SM800A refrigeration controllers. Every firmware version through 5.3.2 is affected. The researchers are in coordinated disclosure with Danfoss, are withholding technical details, and say no CVE identifiers have been assigned. They demonstrated root execution on older firmware; a separate login-path overflow still works on the latest firmware with strict mode enabled. They advise network isolation, citing attacks on exposed Danfoss controllers that began in France on October 11.

Key facts
  • All AK-SM800A versions through 5.3.2 are affected.
  • Impact can include takeover, persistence after reset, and persistent denial of service.
  • The controller process runs as root and lacks stack canaries and PIE.
  • Strict mode, default from firmware 4.0, does not stop the sm_fcgi_app overflow.
  • Secure boot is unused, so a root implant could survive a factory reset.
  • Censys still sees hundreds of Danfoss devices and over 1,000 Copeland and Dixell units.
Analyze this story with Vani AIImpact, who is affected and what defenders should do, in a new chat

Timeline

dated events in the reporting · oldest first
  1. Oct 11, 2026Attacks on exposed Danfoss controllers began in France · Lobsters

What each outlet adds

beyond the shared facts
  • LobstersAdvises VPN, private APN, or IP allowlists over relying on patches.
  • Cyber Security NewsLogin overflow bypasses strict mode; unused secure boot; Copeland and Dixell counts.
Vendors
Danfoss
Products
AK-SM800A
Threat actors
Shahid Kaveh
Countries
FranceIran

Coverage

oldest first · one row per article · UTC
  1. · 2d ago Lobsters · securityFirst report

    Danfoss AK-SM800A through 5.3.2 has six pre-auth RCE flaws

    Midnight Blue found six stack overflows in the latest firmware and says network isolation, not patching, is the real mitigation.

  2. · 9h ago Cyber Security News

    Six pre-auth flaws allow takeover of Danfoss fridge controllers

    Stack overflows hit AK-SM800A firmware through 5.3.2; no CVEs yet, and a login-path bug survives strict mode.