Unauthenticated overflow in Danfoss AK-SM 8xxA, no patch yet

Original title: Danfoss AK-SM 8xxA Series

CISA Advisoriesby CISA ()2 min read
Part of a story covered by 6 sourcesUnpatched Danfoss AK-SM 8xxA flaw can run code without loginMerged summary & timeline
AI summary · x-ai/grok-4.7Summaries by Vani AI

CVE-2026-129713 scores CVSS 9.8; Danfoss says a fix is planned in version 5.5.x, and CISA knows of no exploitation.

CISA says an unauthenticated stack-based buffer overflow in a CGI handler on Danfoss AK-SM 8xxA controllers through 5.4.0 can be triggered by crafted HTTP or HTTPS POST requests. The advisory says this can corrupt memory, restart the web server and hypothetically allow arbitrary code execution with webserver privileges. Danfoss plans to address it in software 5.5.x. CISA reports no known public exploitation.

Unconfirmed: Code execution is described as hypothetical, and CISA says no known public exploitation has been reported.

Key facts
  • CVE-2026-129713 affects Danfoss AK-SM8xxA version 5.4.0 and earlier.
  • CVSS v3.1 base score is 9.8; CVSS v4.0 is 9.3.
  • Authentication is not required to send the crafted POST request.
  • The stated fix is an upcoming 5.5.x release, not yet available.
  • Carlo Meijer of Midnight Blue reported the flaw to CISA.
Security assessment · AI, from the articleNo known exploitation

Impact: Possible unauthenticated code execution as the web server

ProductAffectedFixed in
Danfoss AK-SM 8xxA<=5.4.05.5.x
What to do
  1. 1.Plan to install Danfoss AK-SM 800A software 5.5.x when released.
  2. 2.Keep AK-SM controllers off the internet and isolate them behind firewalls.
Analyze CVE-2026-129713 with Vani AIImpact, affected versions, exploitation, mitigations and detection

Vulnerabilities mentioned

All
CVEVulnerabilityCVSSEPSSSignalsPublished
CVE-2026-129713
Unauthenticated stack overflow in Danfoss AK-SM 8xxA CGI
9.3—

From the original article

2 min read at cisa.gov

View CSAF Summary Successful exploitation of this vulnerability could allow an attacker to execute arbitrary code with webserver privileges. The following versions of Danfoss AK-SM 8xxA Series are affected: AK-SM8xxA <=5. 4.

CISA Advisories

By CISA · cisa.gov

Read the full article at CISA Advisories

A short excerpt; the article and its images belong to the publisher. Summary, key facts and assessment above are AI-written from the article and can be wrong.