Skip to content
NewA calmer, faster ZeroHour

Danfoss AK-SM 8xxA flaw allows unauthenticated remote code execution

Original title: Critical Danfoss Refrigeration Controller Flaw Could Allow Remote Code Execution Without Authentication

Cyber Security Newsby Abinaya ()2 min read
Part of a story covered by 6 sourcesUnpatched Danfoss AK-SM 8xxA flaw can run code without loginMerged summary & timeline
AI summary · x-ai/grok-4.7Summaries by Vani AI

CISA rates CVE-2026-129713 at 9.8 and reports no known exploitation; Danfoss plans a fix in 5.5.x.

CISA advisory ICSA-26-328-03 says Danfoss AK-SM 8xxA refrigeration controllers running version 5.4.0 or earlier have a stack-based buffer overflow in a web-server component that processes requests without login. Corruption can restart the web server or allow code execution with the web server’s permissions. Danfoss advisory DSA-2026-12-01 says version 5.5.x will address it and recommends Strict Mode until then.

Unconfirmed: Danfoss has planned but not stated that version 5.5.x is already available.

Key facts
  • The advisory was published on November 24, 2026, as ICSA-26-328-03.
  • Carlo Meijer of Midnight Blue reported the issue to CISA.
  • The flaw does not require a login, so a password alone does not fix it.
  • Danfoss also plans to remove the option to disable Strict Mode later.
  • A restart could interrupt the management interface even if cooling keeps running.
Security assessment · AI, from the articleNo known exploitation

Impact: Unauthenticated remote code execution as the web server

ProductAffectedFixed in
Danfoss AK-SM 8xxA5.4.0 or earlier5.5.x
What to do
  1. 1.Enable Strict Mode and use strong unique passwords until version 5.5.x is available.
  2. 2.Keep controller web interfaces behind firewalls and off the public internet.
  3. 3.Segment refrigeration networks and use an updated VPN for remote access.
Analyze CVE-2026-129713 with Vani AIImpact, affected versions, exploitation, mitigations and detection

Vulnerabilities mentioned

All
CVEVulnerabilityCVSSEPSSSignalsPublished
CVE-2026-129713
Unauthenticated stack overflow in Danfoss AK-SM 8xxA CGI
9.3—

From the original article

2 min read at cybersecuritynews.com

A critical flaw, CVE-2026-129713, affects Danfoss AK-SM 8xxA refrigeration controllers running version 5. 4. 0 or earlier and could allow unauthenticated remote code execution.

Cyber Security News

By Abinaya · cybersecuritynews.com

Read the full article at Cyber Security News

A short excerpt; the article and its images belong to the publisher. Summary, key facts and assessment above are AI-written from the article and can be wrong.